Customization: | Available |
---|---|
Energy Efficiency Grade: | One |
Heat Temperature: | 50-70°C |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Air Source Heat Pump for Centrol Heat Supply
Parameters for Selection(Reference Only)
Model:NE-F | 325HCR3TEVI-U | 450HCR3TEVI-U | 860HCR3TEVI-U |
Power Supply(V/Ph/Hz) | 380-415V/3N~/50Hz | 380-415V/3N~/50Hz | 380-415V/3N~/50Hz |
Operation Range(ºC) | -25~43 | -25~43 | -25~43 |
[Space Heating] Ambient Temp. (DB/WB): 7°C/6°C, Water Temp. (Inlet/Outlet): 30°C/35°C. | |||
Heating Capacity(kW) | 33.68 | 46.35 | 88.58 |
Power Input(kW)(kW) | 9.36 | 13.17 | 24.07 |
COP | 3.6 | 3.52 | 3.5 |
[Space Heating] Ambient Temp. (DB/WB): 7°C/6°C, Water Temp. (Inlet/Outlet): 50°C/55°C. | |||
Heating Capacity(kW) | 27.28 | 37.54 | 71.75 |
Power Input(kW) | 11.14 | 15.14 | 29.17 |
COP | 2.45 | 2.48 | 2.46 |
[Space Cooling] Ambient Temp. (DB/WB): 35°C / -, Water Temp. (Inlet/Outlet): 12°C/7°C. | |||
Cooling Capacity(kW) | 23.2 | 35 | 65 |
Power Input(kW) | 8.35 | 12.2 | 23.8 |
EER | 2.78 | 2.65 | 2.73 |
Max. Power Input(KW) | 13.5 | 19 | 36 |
Max. Running Current(A) | 25 | 34 | 65 |
Max.Outlet Water Temp.(ºC) | 60 | ||
Rated Water Flow Volume(m³ /h) | 5.79 | 7.97 | 15.23 |
Water Pressure Drop(kpa) | 60 | 40 | 45 |
Sound Pressure at 1m dB(A) | ≤64 | ≤68 | ≤69 |
Water Pipe Connection (inlet/outlet) | G1-1/4"(Male) | G1-1/2"(Male) | 2-1/2"(Flange) |
Refrigerant Type | R410A | R410A | R410A |
Water Connection(inch) | G1-1/4" (male) | G1-1/2" (male) | 2-1/2" (flange) |
Water Proof Class | IPX4 | ||
Net Dimensions(L/W/H)(mm) | 1555×870×1322 | 1500×860×1430 | 1954×957×2021 |
Hydrophilic Aluminum Finned Evaporator
S-shape hydrophilic fin arranged in rows enlarge interface by 30% to ensure high-efficient heating exchange.
Copeland Compressor
A well-known international compressor with high performance is resistant to high temperature, high pressure, and low noise, and has a long service life.
SANHUA Electronic Expansion Valve
Adopt a high-quality pressure switch to adjust refrigerant flow accurately and absorb more heat from the air.
Solution for Large-scale Heating and Cooling
Applied to some large-scale public places in cold climate areas for heating and cooling
Advantages of Sunrise Series(EVI)
By applying EVI technology, the Sunrise Series heat pump can maintain stable working at ambient temperatures as low as -25ºC, or even function better when at a lower temperature.